We can provide lab environment
|
Type |
temperature and humidity |
application industry |
|
conventional constant temperature and humidity laboratory |
18-30 ℃, 45% -70% RH |
textiles, paper, precision manufacturing, and other |
|
low temperature and humidity laboratory |
12-18 ℃, 45% -70% RH |
film preservation, pharmaceutical research, etc. |
|
ultra-low temperature and humidity laboratory |
5-12 ℃ |
biological cultivation, storage libraries, etc. |
|
high temperature and humidity aging room |
30-80 ℃, 40% -95% |
electronics temperature or temperature and humidity aging test |
|
collections library |
18-24 ℃,45-55% |
museums, art centers, logistics, warehousing |
part of the temperature and humidity testing industry standard
|
breakdown |
Textile |
Paper |
plastic |
paint |
Chemical |
|
temperature |
20 ±1 ℃ |
23 ±1 ℃ |
20 ±1 ℃ |
23 ±2 ℃ |
23 ±1 ℃ |
|
relative humidity |
65 ± 2% |
50 ± 2% |
50 ± 3% |
50 ± 5% |
50 ± 2% |
|
cycles |
15 ~ 30 times / h |
15 ~ 30 times / h |
15 ~ 30 times / h |
15 ~ 30 times / h |
15 ~ 30 times / h |
|
air velocity |
≤0.25m/ s |
≤0.3m/ s |
≤0.3m/ s |
≤0.3m/ s |
≤0.3m/ s |
|
new wind supplement |
≥0.5m3/ person. minute |
≥0.5m3/ person. minute |
≥0.5m3/ person. minute |
≥0.5m3/ person. minute |
≥0.5m3/ person. minute |
|
Noise |
≤ 53dB |
≤ 53dB |
≤ 53dB |
≤ 53dB |
≤ 53dB |
|
national standard |
GB6529 |
GB10739 |
GB/T2918 |
GB9278 |
GB10739 |
|
international standards |
ISO139 |
ISO187 |
ISO291 |
ISO3270 |
ISO187 |
design methods and points
meet ISO design a hygrostat and GB standards laboratory method and the most important point is to grasp the design. Based on our many years of practical experience, we believe that the application of dynamic control method and system is appropriate, that constantly adjust the temperature and humidity values to reach the pre-set standard value control methods.
|
1. temperature and humidity control range |
2. temperature and humidity control accuracy |
3. cleanliness requirements |
|
4. illumination requirements |
5. thermal moisture content range of the device |
6. air conditioning back to the wind |
|
7. balancing measures air pressure of |
8. introduced the need for new Wind |
9. necessity exhaust system |
|
10. insulation measures |
11. configuration facilities and power of |
12. static, vibration and noise |
|
13. equipment space and air-conditioned rooms |
14. arrangement of access routes and changing the buffer |
15. sufficient maintenance space |
|
16. ceiling height and floor load |
17. pollution, pollution prevention |
18. installation and operating costs of the measure |
|
19. aesthetic requirements |
20. installation cost / schedule control |
21. operating costs |
|
22. maintenance & elasticity factor |
|
|
constant temperature and humidity air-conditioning systems laboratory equipment performance parameters
| performance parameters | Unit | 1 | 2 | 3 | 4 | 5 |
| laboratory area | m 2 | 10 ~ 30 | 30 ~ 50 | 50 ~ 70 | 70 ~ 100 | 100 ~ 130 |
| air conditioning cooling capacity | k W | 13 | 20 | 27 | 41 | 53 |
| indoor fan flow | m 3 / h | 2 800 | 4500 | 5600 | 8600 | 11500 |
| temperature control range | ℃ | 18 ~ 25 | 18 ~ 25 | 18 ~ 25 | 18 ~ 25 | 18 ~ 25 |
| temperature sensitivity | ℃ | ± 1 | ± 1 | ± 1 | ± 1 | ± 1 |
| heater power | k W | 6 | 9 | 12 | 18 | 24 |
| humidifier power | k W | 6 | 6 ~ 9 | 9 | 9 ~ 12 | 15 |
| humidification | kg / h | 8 | 8 ~ 12 | 12 | 12 ~ 16 | 20 |
| outdoor fan | Number of units × Power (kW) | 1 × 0.36 | 1 × 0.72 | 1 × 0.98 | 2 × 0.72 | 2 × 0.98 |
| outdoor compressor | Number of units × Power (kW) | 1 × 3.7 | 1 × 5.6 | 1 × 7.5 | 2 × 5.6 | 2 × 7.5 |
| fan power | hp | 1.5 | 2 | 3 | 5 | 7.5 |
| indoor fan | Type | Centrifugal | Centrifugal | Centrifugal | Centrifugal | Centrifugal |